Baxi Potterton LPG Service Manual Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
13
6.0 System Details
© Baxi Heating UK Ltd 2008
Stop
Valve
Double
Check
Valve
Mains
Cold
Inlet
CH
Return
Temporary
Hose
Stop
Valve
Fig. 3
Filling Loop for
Sealed Systems
6.4 System Filling and Pressurising
Sealed Systems
1. A filling point connection on the central heating return
pipework must be provided to facilitate initial filling and
pressurising and also any subsequent water loss
replacement/refilling.
2. The filling method adopted must be in accordance with all
relevant water supply regulations and use approved equipment.
3. Your attention is drawn to the current edition of I.S. 813
“Domestic Gas Installations”.
4. The sealed primary circuits may be filled or replenished by
means of a temporary connection between the circuit and a
supply pipe, provided a ‘Listed’ double check valve or some other
no less effective backflow prevention device is permanently
connected at the inlet to the circuit and the temporary
connection is removed after use.
‘Semi - Sealed’ Systems
1. ‘Semi - Sealed’ systems require the use of a suitable header
tank and ball cock arrangement to charge and provide subsequent
replenishment of the system.
2. The tank must be placed to provide sufficient head in order to
ensure a minimum system pressure of 0.2 bar.
3. A suitable non - return valve must be fitted in the pipework
between the header tank and heating system.
6.5 Expansion Vessel
1. The appliance expansion vessel is pre-charged to 0.5 bar. The
vessel is suitable for correct operation for system capacities up to
125 litres. For greater system capacities an additional expansion
vessel must be fitted. Refer to BS 7074 Pt 1. For IE, the current
edition of I.S. 813 “Domestic Gas Installations”.
6.6 Pressure Relief Valve (Fig. 4)
1. The pressure relief valve is set at 3 bar, therefore all pipework,
fittings, etc. should be suitable for pressures in excess of 3 bar and
temperature in excess of 100°C.
2. The pressure relief discharge pipe should be not less than 1/2”
dia, run continuously downward, and discharge outside the
building, preferably over a drain. It should be routed in such a
manner that no hazard occurs to occupants or causes damage to
wiring or electrical components. The end of the pipe should
terminate facing down and towards the wall.
3. The discharge must not be above a window, entrance or other
public access. Consideration must be given to the possibility that
boiling water/steam could discharge from the pipe.
Fig. 3a
‘Semi-Sealed’
System
CH
Return
Header Tank
Non-Return
Valve
Fig. 4
Pressure Relief Valve
Discharge Pipe
Page view 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 55 56

Comments to this Manuals

No comments